Description
The Fire-Lite ECC-RM is an optional Remote Microphone that is compatible with the ECC-50/100(E) Emergency Command Center for fire protection applications. It is part of a family of external remote consoles that allows for extending the operator interface to remote locations within a building. It is house in a cabinet with a keyed or an optional thumb lock to limit access to qualified personnel. The ECC-RM remote microphone allows for ALL CALL paging to be broadcast over the speaker circuits when depressing the microphone’s push-to talk switch. The RM requires an external data bus connection, an external audio riser connection, and an external operator interface power connection (24 Volts DC) from the ECC-50/100 main console.
Also this system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity 93% ± 2% RH at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system’s standby batteries and the electronic components may be adversely affect by extreme temperature ranges and humidity. Therefore, it is recommend that this system and its peripherals be install in an environment with a normal room temperature of 15-27º C/60-80º F.
- Features / Specifications
- Modular design for maximum system flexibility and easy expansion.
- Supports both Class A (Style Z) and Class B (Style Y) wiring.
- A maximum of eight ECC-RMs can be connect to an ECC-50/100(E) primary operating console.
- Built-in microphone with push-to-talk feature that can be use for ALL CALL paging.
- Simple and straightforward user interface.
- 24VDC non-resettable power from the ECC-50/ 100(E).(Non-supervised).
- Download the Specification sheet in *.pdf format