Description
The Fire-Lite ECC-CE4 adds four audio circuits to theECC-50DA(E) and ECC-125DA(E). The ECC-CE4 mounts inside the ECC-50/125DA(E) cabinet. The ECC-CE4 is compatible with the Fire-Lite
ECC-50/100 Emergency Command Center and their remote amplifiers. Refer to the ECC and ECC-50/125DA Manuals, P/N LS10001-000FL-E and LS10027-000FL-E, for more information. Connect the supplied audio expander cable harness (PN 130426) from the connector labeled Audio Expander on the ECC-50/125DA to the connector on the ECC-CE4.Remove AC power from the ECC-50/125DA control panel and disconnect the backup batteries. Using the four supplied screws, mount the ECC-CE4 in the ECC-50/125DA cabinet. Wire speakers for Class B (Style Y) supervision as shown in Figure 3 or for Class A (Style Z) wiring. Restore AC power and reconnect the backup batteries.
Besides it features a modular design with removable terminal blocks for easy service, 50W of audio power (expandable to 100W), and a 2A Notification Appliance Circuit (NAC) output. Also it allows for system expansion and compatibility with various audio protocols like System Sensor, Wheelock, and Gentex.
- Features / Specifications
- Allows for system flexibility and easy expansion.
- Standby Current: 20 mA.
- Alarm Current: 180 mA.
- Works with the system’s audio power to provide 50W of 25V RMS audio power (expandable to 100W).
- Includes 520 Hz square wave tones for audio signaling.
- Features removable terminal blocks for easier maintenance and replacement.
- Download the Specification sheet in *.pdf format