Description
In general, the Fire-Lite MMF-300 Monitor Module is intended for use in intelligent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. It provides either a two-wire or four-wire fault-tolerant Initiating Device Circuit (IDC) for normally-open-contact fire alarm and supervisory devices. Also, the module has a panel-controlled LED indicator. The Fire-Lite MMF-300(A) can be use to replace M300(A) modules in existing systems.
Furthermore, use to monitor a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally- open dry-contact alarm activation devices. May also be use to monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit may be wire as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 47K Ohm End-of-Line Resistor (provided) terminates the Style B circuit. No resistor is require for supervision of the Style D circuit.
- Features / Specifications
- Built-in type identification automatically identifies this device as a monitor module to the control panel
- Powered directly by two-wire SLC loop. No additional power required
- High noise (EMF/RFI) immunity
- SEMS screws with clamping plates for ease of wiring
- Direct-dial entry of address: 01 – 159 on MS-9600 series panels, 01 – 99 on other compatible systems
- LED flashes during normal operation and latches on steady to indicate alarm