In general, the Honeywell AMM-2F addressable monitor module is a single Style B, Class B initiating device circuit (IDC) with a 47KW end-of-line resistor. Besides, this module provides an address for any device or group of devices connected to this circuit on the signaling line circuit (SLC) of the Gamewell-FCI addressable series fire alarm control panel. Any initiating device with normally open (N.O.) dry contacts may be made addressable when connected to the AMM-2F module.
The initiating device circuit of the AMM-2F can support a maximum line resistance of up to 40 ohms allowing the use of linear heat detection devices. Additionally, the compact size facilitates the installation of the module inside manual stations; also mounting boxes of various types of alarm initiating devices.
The Honeywell AMM-2F module can be programm to provide a wide variety of input functions to the Gamewell-FCI addressable series fire alarm control panels. It can be identify as a manual station, heat detector, plenum detector, waterflow switch, tamper switch, N.O. contact, smoke detector, projected beam smoke detector, sub loop, remote zone, etc. Also, it can also serve as a remote system silence, system reset, system acknowledge or drill switch. It is even possible to customize its device type to meet specific job requirements.
- Features / Specifications
- Compact size allows easy installation
- Class B, Style B, initiating circuit
- 40 Ohm line resistance for each initiating device circuit
- Connects to any normally open dry contact device
- Download the Specification sheet in *.pdf format